Salaisons Dijonnaise

Agrifood industry

Initial situation

Consumption : 8 336L of domestic hot water per day
Positive cold : R404a system – Cooling capacity = 200 000W & Heat rejection = 300 000W (at -10/+48°C)

Proposal / study

Equipment for positive cold unit : 2 x 70 kW Boostherms, branch circuit
Installation of 2 x 2 000L buffer tanks upstream from a 1 500L electric water heater

Forecast return on investment at time of study : 2.2years

Measurements taken

Measurement dates : 17/09/15 to 10/05/17

Average energy recovered per day : 366.3 kWh/day
Annual energy savings : 98 901 kWh/year

Total annual savings : approx. €8,901/year, i.e., equiv. to 30.66 tonnes of CO2/year

Actual return on investment : 2.1years