Pop Kfé restaurant

Hotel business

Initial situation

Consumption : 2 505L of domestic hot water per day
Positive cold : R404a system – Cooling capacity = 12 250W & Heat rejection = 18 550W (at -10/+48°C)
Negative cold : R404a unit – Cooling capacity = 1 400W & Heat rejection = 3 000W (at -30/+45°C)

Proposal / study

Equipment for positive cold unit : Boostherm 20kW
Equipment for negative cold unit : Boostherm 5kW
Installation of a 1 000L combined storage tank

Forecast return on investment at time of study : 4years

Measurements taken

Measurement dates : 20/07/13 to 28/06/16

Average energy recovered per day : 89,6kWh/day
Annual energy savings : 32 704kWh/year

Total annual savings : approx. €3 633/year, i.e., equiv. to 0,668 tonnes of CO2/year

Actual return on investment : 3,7years