Alsacienne de Restauration

Central kitchens

Initial situation

Consumption : 6 273L of domestic hot water per day
Positive cold : R404a system – Cooling capacity = 90 000W & Heat rejection = 126 000W (at -10/+48°C)

Proposal / study

Equipment for positive cold unit : 2 x 70 kW Boostherms, parallel circuit
Installation of a 5 000L buffer tank + a 5 000L electric tank for auxiliary heating

Forecast return on investment at time of study : 3.8years

Measurements taken

Measurement dates: 28/11/17 to 22/01/18

Average energy recovered per day : 167.3 kWh/day
Annual energy savings : 43 491 kWh/year

Total annual savings : approx. €3,914/year, i.e., equiv. to 13.48 tonnes of CO2/year

Actual return on investment : 2.7years